Safety

The chamber heater controlled by this plugin can reach temperatures that soften or ignite materials and can burn skin. PandaBreath layers several independent safety mechanisms so that a single failure — a stale connection, an unreachable printer, an over-temperature reading — does not leave the chamber heating unattended. This page documents each mechanism, how it behaves, and how to recover from it.

The plugin is an assistant, not a replacement for the device

The Panda Breath firmware enforces its own limits. PandaBreath mirrors those limits and adds OctoPrint-side guards, but you remain responsible for safe operation, adequate ventilation, and not leaving prints unattended.

Observe-only mode

Observe-only is the default and the single most important safety setting.

  • The adapter connects, binds, and polls the device, but suppresses every write frame.
  • The controller stops issuing its own heater on/off commands.
  • The HTTP API rejects mutating commands with HTTP 409 (Conflict).

Keep observe-only enabled until you have confirmed, from the logs and the live status, that the plugin reads your device correctly. Only then disable it to allow write control.

Emergency stop still works in observe-only

The emergency-stop heater_off frame is on the observe-safe whitelist, so it always reaches the device even while normal writes are suppressed.

Safety lock

The safety lock is a single internal flag that, when engaged, forces the heater off and blocks power-on. It can be triggered for five distinct reasons. Turning the heater off is always allowed regardless of the lock.

Reason (last_safety_reason) Trigger Releases
user Operator pressed Lock Manually, via Unlock
estop Emergency stop Manually, via Unlock
over_temp Chamber exceeded the configured max_temp Manually, via Unlock
timeout Watchdog saw no data for timeout_seconds Auto, on the next fresh status frame
printer_link Paired printer is binding or unreachable Auto, once the printer is bound again

The two auto-releasing locks (timeout, printer_link) clear themselves when the underlying condition resolves. The three manual locks (user, estop, over_temp) stay engaged until you press Unlock — they represent a deliberate or hard-fault state that an operator should acknowledge.

Locks do not override each other

An auto-releasing lock never clobbers a manual one. If you engage a user lock and the printer link then drops and recovers, the user lock survives — only the operator can release it.

Emergency stop

Emergency stop is a hard stop that shuts the heater down regardless of observe-only. It sends a single heater_off frame — the same mechanism the Panda Breath's own WebUI "Work Mode off" toggle uses, which is the only stop the device firmware exposes. The firmware then stops any running dry cycle and turns the heater off internally.

  • Exposed as a navbar button (toggle with the navbar_estop_enabled setting).
  • Engages a manual-class lock (estop) that must be released manually.
  • Never surfaces transport errors: the internal state flips to locked even if the wire frame fails to send, so the safety guarantee holds.

The chamber must not heat unless the paired printer is reachable. The device reports a printer_state in every status frame:

printer_state Meaning Heating
2 Binding — link still being established Blocked
3 Bound — printer reachable Allowed
4 Unreachable — printer cannot be reached Blocked
(absent) Older firmware that omits the field Not gated

While the link is binding (2) or unreachable (4):

  • set_heater(on=True) is refused with HTTP 423 (Locked).
  • If the heater was already running, the status loop engages a printer_link lock and forces a heater_off frame to the device.
  • The power-on control in the UI is disabled, with an explanatory warning.

When the printer becomes bound (3) again, the printer_link lock auto-releases and power-on is permitted.

Over-temperature cutoff

Every status frame is checked against the configurable max_temp (default 70 °C). If the chamber reading exceeds it, the controller engages an over_temp lock and shuts the heater off. This is a manual lock: it requires an operator Unlock, because exceeding the hard limit indicates the chamber ran hotter than intended and warrants attention.

max_temp also caps the upper bound of any target temperature you set, so the plugin refuses to request a target above the limit in the first place.

Watchdog (stale-data timeout)

A background watchdog tracks the time since the last received frame. If no data arrives for timeout_seconds (default 15 s), it engages a timeout lock and shuts the heater off — heating blind, with no telemetry, is unsafe.

This lock auto-releases on the next fresh status frame, because renewed data flow means the condition has resolved on its own.

Permissions

PandaBreath registers three OctoPrint permissions so administrators can scope who may do what:

Permission Allows
View chamber status Reading the chamber state (read-only)
Control chamber heater Changing target, mode, and heater state
Administer chamber lock Locking/unlocking the safety interlock

Grant control and admin permissions only to trusted operators.

Device input limits

The plugin mirrors the firmware's reverse-engineered limits and clamps or rejects out-of-range input before sending a frame:

Setting Min Max
Chamber target (°C) 0 60 (further capped by max_temp)
Filter threshold (°C) 0 120
Heater threshold (°C) 40 120
Dry target (°C) 40 60
Dry timer (hours) 1 99

Recovery checklist

Symptom Likely lock Action
Power-on refused, "printer link" warning printer_link Wait for the printer to become reachable; the lock clears itself
Heater shut off, no recent status timeout Check the device connection; a fresh frame auto-clears it
Heater shut off after a hot reading over_temp Investigate the cause, then press Unlock
Locked after pressing Stop estop / user Press Unlock when ready to resume

See also: Configuration · Troubleshooting